Input/OutputModule
• ADM loop technology with
Apollo/Discovery protocol
• One line-monitored input and one
dry relay output 230VAC
• Setting of module address by means
of address switch
• Integrated dual-isolator
• Status LEDs for input and output
Description
The addressable Module 55000-875 serves for the line- means of a relay output with a dry change-over contact,
monitored integration of a contact detector, such as a via the ADM loop.
manual call point, a sprinkler system contact or a su- The address is easily selected by means of a built-in DIL
pervising contact, into the bidirectional communication switch. Status LEDs indicate the condition of input and
on the ADM loop with Apollo/Discovery protocol. Fur- output. The module has an integrated dual-isolator and
thermore, it can be used to actuate external devices by is fitted into a plastic case.
Specifications
Operating voltage
Current consumption
Contact rating
Ambient temperature
Dimensions L × W × H
Colour
Supply through loop voltage
approx. 1.25mA (quiescent)
2A/48VDC or 5A/230VAC
-20°C to +70°C
150 × 90 × 48 (mm)
white
Weight
240g
Order number
Order name
249078
Module 1xSurv.In 1xRel.Out-230/Apo 55000-875
Building Safety. Building Security.
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
55000-875_DBL_LST_EN_0804.PDF • PAGE 1
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
|
Kustom Stereo Amplifier 12 Gauge User Manual
LG Electronics Flat Panel Television 22LQ63OH User Manual
Liebherr Refrigerator 131113 7085462 01 User Manual
Life Fitness Elliptical Trainer Lifecycle 8500 User Manual
Lightolier Indoor Furnishings WLRN124120SB User Manual
Magnavox Portable CD Player MPC210BL User Manual
Makita Drill 6013BR User Manual
Makita Trimmer UML2OOD User Manual
Marantz Projection Television PV6480W User Manual
Matrox Electronic Systems Computer Drive MKey 100 User Manual